|本期目录/Table of Contents|

[1]杨文涛,胡馨月,任晓锋,等.基于灰色关联分析的变压器油池火灭火有效性评估*[J].中国安全生产科学技术,2023,19(3):177-182.[doi:10.11731/j.issn.1673-193x.2023.03.026]
 YANG Wentao,HU Xinyue,REN Xiaofeng,et al.Effectiveness evaluation on fire extinguishing of transformer pool fire based on grey correlation analysis[J].JOURNAL OF SAFETY SCIENCE AND TECHNOLOGY,2023,19(3):177-182.[doi:10.11731/j.issn.1673-193x.2023.03.026]
点击复制

基于灰色关联分析的变压器油池火灭火有效性评估*
分享到:

《中国安全生产科学技术》[ISSN:1673-193X/CN:11-5335/TB]

卷:
19
期数:
2023年3期
页码:
177-182
栏目:
职业安全卫生管理与技术
出版日期:
2023-03-31

文章信息/Info

Title:
Effectiveness evaluation on fire extinguishing of transformer pool fire based on grey correlation analysis
文章编号:
1673-193X(2023)-03-0177-06
作者:
杨文涛胡馨月任晓锋高进东张江石
(1.中国矿业大学(北京) 应急管理与安全工程学院,北京 100083;
2.中国安全生产科学研究院,北京 100012)
Author(s):
YANG Wentao HU Xinyue REN Xiaofeng GAO Jindong ZHANG Jiangshi
(1.School of Emergency Management and Safety Engineering,China University of Mining and technology (Beijing),Beijing 100083,China;
2.China Academy of Safety Science and Technology,Beijing 100012,China)
关键词:
有效性评估图像处理灰色关联分析油池火
Keywords:
effectiveness evaluation image processing grey correlation analysis pool fire
分类号:
X932;X921
DOI:
10.11731/j.issn.1673-193x.2023.03.026
文献标志码:
A
摘要:
为对比不同灭火系统扑灭变压器油池火灾有效性,提升变压器油池火灭火效能,从效能评估工具、灭火临界参数、行业法规中提取并确定变压器油池火灭火有效性评估指标集,包括3个观测变量,6个具体指标。采用Otsu’s算法处理火灾图像确定火焰面积,通过层次分析法确定各观测变量和具体指标权重,应用灰色关联法构建变压器油池灭火有效性评估模型。以水喷雾、细水雾、泡沫-水喷雾以及泡沫-细水雾扑灭变压器油池火为例,分别计算4种不同灭火系统下的灭火有效性。研究结果表明:灭火方案有效性为泡沫细水雾(1.000)>纯水细水雾(0.653)>泡沫水喷雾(0.447)>纯水水喷雾(0.333)。该评估模型可以将消防监测终端采集的消防大数据与人工智能技术有效结合,有助于提升变压器消防安全管理智能化水平。
Abstract:
In order to compare the effectiveness of different fire-fighting systems in extinguishing the oil pool fire of transformers,and improve the fire extinguishing efficiency of transformer oil pool fire,the index set of the effectiveness evaluation on fire extinguishing of transformer pool fire was extracted from the effectiveness evaluation tools,fire extinguishing critical parameters and industrial regulations and determined,including 3 observation variables and 6 specific indexes.The Otsu’s algorithm was used to process the fire image to determine the flame area,then the weights of each observation variable and specific index were determined by analytic hierarchy process,and the grey correlation method was used to construct the effectiveness evaluation model for the extinguishing of transformer oil pool fire.Taking the water spray,water mist,foam-water spray and foam-water mist extinguishing transformer oil pool fire as examples,the fire extinguishing effectiveness under four different fire extinguishing systems was calculated respectively.The results showed that the effectiveness of the fire extinguishing scheme is foam water mist (1.000)>pure water mist (0.653)>foam water spray (0.447)>pure water spray (0.333).The evaluation model can effectively combine the fire big data collected by the fire monitoring terminals with the artificial intelligence technology,which is helpful to improve the intelligent level of fire safety management on the transformers.

参考文献/References:

[1]赵金龙,袁杰,田逢时,等.初始油温对变压器油燃烧特性的影响[J].化工学报,2020,71(7):3379-3386. ZHAO Jinlong,YUAN Jie,TIAN Fengshi,et al.Effect of initial fuel temperature on burning characteristics of transformer oil[J].CIESC Journal,2020,71(7):3379-3386.
[2]LIU Y,LI B,WU C P,et al.Effectiveness test and evaluation of transformer fire extinguishing system[J].Fire Technology,2022,58(5):3167-3190.
[3]CHOI B,HAN Y S,KIM M B.A fire scenario for application of water mist system to an indoor power transformer room[J].Fire Science and Engineering,2005,19(3):52-57.
[4]PEI Z,WANG X,WANG Z,et al.Experimental study on transformer oil pool fire sup-pression by water mist[C]//The 10th Asia-Oceania Symposium on Fire Science and Technology,2015.
[5]CHEN W,HU S,TANG L,et al.Research review on transformer fire protection technology[J].IOP Conference Series Earth and Environmental Science,2019,310:022022.
[6]SUN R B,YANG X,WANG J C,et al.Experimental study on axial temperature profile of jet fire of oil-filled equipment in substation[J].Processes,2021,9(8):1460.
[7]羡学磊,蔡海宇,董海斌,等.气体灭火系统可靠性评估方法[J].消防科学与技术,2017,36(8):1101-1104. XIAN Xuelei,CAI Haiyu,DONG Haibin,et al.Reliability evaluation method of gas fire extinguishing system[J].Fire Science and Technology,2017,36(8):1101-1104.
[8]伊程毅,董海斌,刘连喜,等.气体灭火系统安全性评估方法[J].消防科学与技术,2018,37(7):985-988. YI Chengyi,DONG Haibin,LIU Lianxi,et al.Safety evaluation method of gas fire extinguishing system[J].Fire Science and Technology,2018,37(7):985-988.
[9]颜峻,疏学明,吴津津.建筑消防水系统灭火可靠性动态评估模型研究[J].火灾科学,2018,27(4):254-260. YAN Jun,SHU Xueming,WU Jinjin.Reliability dynamic assessment model of water fire-extinguishing system[J].Fire Safety Science,2018,27(4):254-260.
[10]马栋,夏登友,陈震,等.基于云模型的灭火救援决策效能评估[J].消防科学与技术,2016,35(1):104-108. MA Dong,XIA Dengyou,CHEN Zhen,et al.Effectiveness evaluation of firefighting and rescue decision making based on cloud model[J].Fire Science and Technology,2016,35(1):104-108.
[11]ZHOU Y,BU R W,GONG J H,et al.Assessment of a clean and efficient fire-extinguishing technique:continuous and cycling discharge water mist system[J].Journal of Cleaner Production,2018,182:682-693.
[12]陈光,景伟,王志刚,等.火源功率对室内变压器火灾燃烧特性影响研究[J].中国安全生产科学技术,2019,15(7):186-192. CHEN Guang,JING Wei,WANG Zhigang,et al.Study on influence of fire source power on combustion characteristics of indoor transformer fire[J].Journal of Safety Science and Technology,2019,15(7):186-192.
[13]陈晟,邓洁清,鞠振福,等.变压器油池火燃烧规律的实验研究[J].中国安全生产科学技术,2020,16(8):63-68. CHEN Sheng,DENG Jieqing,JU Zhenfu,et al.Experimental study on combustion laws of transformer oil pool fire[J].Journal of Safety Science and Technology,2020,16(8):63-68.
[14]LU J Z,LIANG P,CHEN B H,et al.Investigation of the fire-extinguishing performance of water mist with various additives on typical pool fires[J].Combustion Science and Technology,2020,192:4,592-609.
[15]沈萍.宝钢某工程户外大型变压器水喷雾灭火系统设计[J].给水排水,2014,40(2):88-90. SHEN Ping.Design of the water spay fire control system for an outdoor large scale transformer in Bao Steel[J].Water & Wastewater Engineering,2014,40(2):88-90.
[16]张江石.行为安全管理中的数学模型及应用[M].北京:煤炭工业出版社,2016.
[17]陈光.水喷雾与泡沫喷雾灭油池火实验特性对比研究[J].消防科学与技术,2021,40(3):372-374. CHEN Guang.Comparative study on the experimental characteristics of water spray and foam spray in extinguishing pool fire [J].Fire Science and Technology,2021,40(3):372-374.

相似文献/References:

[1]郭志宇,郭安宁,白雪见,等.基于视频监控系统的突发灾害应急评估技术可行性研究[J].中国安全生产科学技术,2017,13(5):122.[doi:10.11731/j.issn.1673-193x.2017.05.020]
 GUO Zhiyu,GUO Anning,BAI Xuejian,et al.Feasibility study on emergency assessment technology of sudden disaster based on video surveillance system[J].JOURNAL OF SAFETY SCIENCE AND TECHNOLOGY,2017,13(3):122.[doi:10.11731/j.issn.1673-193x.2017.05.020]

备注/Memo

备注/Memo:
收稿日期: 2022-10-07
* 基金项目: 国家重点研究计划项目(2021YFC3001201)
作者简介: 杨文涛,硕士,高级工程师,主要研究方向为安全文化、安全评价、职业危害评价、城市安全风险评估、安全管理、应急管理等。
通信作者: 胡馨月,硕士,主要研究方向为安全文化、安全评价、城市安全风险评估、安全管理等。
更新日期/Last Update: 2023-04-12