|本期目录/Table of Contents|

[1]何坤,徐林志,陆兆勇,等.压缩空气泡沫扑救大型油类火灾全尺寸实验研究*[J].中国安全生产科学技术,2022,18(9):154-159.[doi:10.11731/j.issn.1673-193x.2022.09.022]
 HE Kun,XU Linzhi,LU Zhaoyong,et al.Full-scale experimental study on extinguishing large oil fire using compressed air foam[J].JOURNAL OF SAFETY SCIENCE AND TECHNOLOGY,2022,18(9):154-159.[doi:10.11731/j.issn.1673-193x.2022.09.022]
点击复制

压缩空气泡沫扑救大型油类火灾全尺寸实验研究*
分享到:

《中国安全生产科学技术》[ISSN:1673-193X/CN:11-5335/TB]

卷:
18
期数:
2022年9期
页码:
154-159
栏目:
职业安全卫生管理与技术
出版日期:
2022-09-30

文章信息/Info

Title:
Full-scale experimental study on extinguishing large oil fire using compressed air foam
文章编号:
1673-193X(2022)-09-0154-06
作者:
何坤徐林志陆兆勇徐学军邓锡中廖克斌韩月杨志立程旭东
(1.中国科学技术大学 火灾科学国家重点实验室,安徽 合肥 230026;
2.广东瑞霖特种设备制造有限公司,广东 肇庆 526108;
3.广西消防救援总队,广西 南宁 530201;
4.南宁消防救援支队,广西 南宁 530028)
Author(s):
HE Kun XU Linzhi LU Zhaoyong XU Xuejun DENG Xizhong LIAO Kebin HAN Yue YANG Zhili CHENG Xudong
(1.State Key Laboratory of Fire Science,University of Science and Technology of China,Hefei Anhui 230026,China;
2.Guangdong Ruilin Special Equipment Manufacturing Company,Zhaoqing Guangdong 526108,China;
3.Guangxi Fire and Rescue Corps,Nanning Guangxi 530201,China;
4.Nanning Fire and Rescue Detachment,Nanning Guangxi 530028,China)
关键词:
全尺寸灭火实验大型油池火灾压缩空气泡沫系统灭火性能
Keywords:
full-scale fire extinguishing experiment large oil pool fire compressed air foam system fire extinguishing performance
分类号:
X932
DOI:
10.11731/j.issn.1673-193x.2022.09.022
文献标志码:
A
摘要:
为验证压缩空气泡沫扑救大型火灾的有效性,分别开展225 m2甲醇和450 m2重油油池火灭火实验,采用压缩空气泡沫系统搭配消防机器人远距离喷射压缩空气泡沫的灭火方法,分析该方法的灭火效能。研究结果表明:压缩空气泡沫系统可以实现远距离灭火,压缩空气泡沫的施加可以有效降低油池内燃料温度、火场温度以及油池附近热辐射强度。在压缩空气泡沫系统混合液流量为3 900 L/min时,距离油池边缘29 m条件下扑救450 m2全尺寸重油火灾的灭火时间为130 s,灭火阶段水和3%泡沫液的消耗量分别为8 233 L和273 L;在压缩空气泡沫系统混合液流量为3 600 L/min时,距离油池边缘不小于35 m条件下扑救225 m2全尺寸甲醇火灾的灭火时间为231 s,灭火阶段水和6%泡沫液的消耗量分别为12 962 L和808 L。研究结果对提升扑救大型油池火灾的作战能力具有重要意义。
Abstract:
In order to verify the effectiveness of compressed air foam in extinguishing the large scale fires,the fire extinguishing experiments of 225 m2 methanol and 450 m2 heavy oil pool fires were carried out respectively.The method using the compressed air foam system cooperated with the fire fighting robot to inject the compressed air foam remotely was adopted,and the fire extinguishing efficiency of the method was analyzed.The results showed that the compressed air foam system could achieve the long-distance fire extinguishing,and the application of compressed air foam could effectively reduce the fuel temperature in the oil pool,fire field temperature and thermal radiation intensity near the oil pool.When the mixed liquid flow rate of the compressed air foam system was 3 900 L/min,the extinguishing time of the 450 m2 full-scale heavy oil fire was 130 s under the condition of 29 m from the edge of oil pool,and the consumption amount of water and 3% foam liquid in the extinguishing stage was 8 233 L and 273 L,respectively.When the mixed liquid flow rate of the compressed air foam system was 3 600 L/min,the extinguishing time of the 225 m2 full-scale methanol fire was 231 s under the condition of no less than 35 m from the edge of oil pool,and the consumption amount of water and 6% foam liquid in the extinguishing stage was 12 962 L and 808 L,respectively.The results of this study are of great significance to improve the combat capability of extinguishing large oil pool fires.

参考文献/References:

[1]司海涛.大型浮顶罐主要安全事故类型及原因[J].油气储运,2013,32(9):1029-1033. SI Haitao.Accident’s type and cause of large-scale floating roof tank[J].Oil & Gas Storage and Transportation,2013,32(9):1029-1033.
[2]陈涛,胡成,包志明,等.不同气源压缩气体泡沫灭浮顶罐密封圈火灾性能比较[J].中国安全生产科学技术,2020,16(3):98-104. CHEN Tao,HU Cheng,BAO Zhiming,et al.Comparison on fire extinguishing performance of compressed gas foam with different gas sources for rim seal fire of floating roof tanks[J].Journal of Safety Science and Technology,2020,16(3):98-104.
[3]秘义行,智会强,周在云,等.低倍数泡沫灭火系统若干问题探讨[J].消防科学与技术,2015(5):600-603. MI Yixing,ZHI Huiqiang,ZHOU Zaiyun,et al.Research on some problems of low-expansion foam extinguishing system[J].Fire Science and Technology,2015(5):600-603.
[4]邓天刁,刘长春,黄林远,等.正压式泡沫灭火技术的研究进展[J].中国安全科学学报,2019(10):64-70. DENG Tiandiao,LIU Changchun,HUANG Linyuan,et al.Research progress of positive pressure foam extinguishing technology[J].China Safety Science Journal,2019(10):64-70.
[5]徐学军.压缩空气泡沫管网输运特性及其在超高层建筑中应用研究[D].合肥:中国科学技术大学,2020.
[6]XU X,HE K,ZHANG H,et al.Full-scale Experimental study on flow and fire extinguishing characteristics of compressed air foam[C]// 2019 9th International Conference on Fire Science and Fire Protection Engineering (ICFSFPE).Chengdu,China:IEEE,2019:1-5.
[7]KIM A K,DLUGOGORSKI B Z.Multipurpose overhead compressed-air foam system and its fire suppression performance [J].Journal of Fire Protection Engineering,1996,8(3):133-150.
[8]KIM A K,CRAMPTON G P.Application of a newly-developed compressed-air-foam fire suppression system[C]// Interflam 2001,9th International Fire Science and Engineering Conference.Edinburgh,UK:Interscience Communications,2001:1219-1224.
[9]KIM A K,CRAMPTON G P.Evaluation of the fire suppression effectiveness of manually applied compressed-air-foam (CAF) system[J].Fire Technology,2012,48(3):549-564.
[10]包志明,陈涛,傅学成,等.压缩空气泡沫抑制水溶性液体火的有效性研究[J].中国安全生产科学技术,2013,9(3):9-12. BAO Zhiming,CHEN Tao,FU Xuecheng,et al.Study on the efficiency of suppressing water-soluble liquid fire by compressed air foam[J].Journal of Safety Science and Technology,2013,9(3):9-12.
[11]陈涛,胡成,包志明,等.公路隧道压缩空气泡沫系统灭油池火实验研究[J].中国安全生产科学技术,2017,13(7):30-36. CHEN Tao,HU Cheng,BAO Zhiming,et al.Experimental study on extinguishing of pool fire with compressed air foam system in road tunnel[J].Journal of Safety Science and Technology,2017,13(7):30-36.
[12]陆强,傅学成,包志明,等.压缩空气泡沫抑制小型油罐火的试验研究[J].警察技术,2015(6):89-92.
[13]郎需庆,牟小冬,尚祖政,等.压缩空气泡沫灭火系统在罐区的应用探讨[J].消防科学与技术,2016,35(6):815-817. LANG Xuqing,MU Xiaodong,SHANG Zuzheng,et al.Application fo fixed compressed air foam system on oil tanks[J].Fire Science and Technology,2016,35(6):815-817.
[14]WANG K,FANG J,SHAH H R,et al.A theoretical and experimental study of extinguishing compressed air foam on an n-heptane storage tank fire with variable fuel thickness[J].Process Safety and Environmental Protection,2020,138:117-129.
[15]李世环.压缩空气泡沫灭火系统在石油化工储罐消防安全中的应用[J].化工管理,2022(3):119-121.
[16]高阳.压缩空气泡沫隔热防护性能研究[J].消防科学与技术,2019,38(8):1120-1123. GAO Yang.Study on thermal insulation and protection performance of compressed air foam[J].Fire Science and Technology,2019,38(8):1120-1123.
[17]朱建华,褚家成.池火特性参数计算及其热辐射危害评价[J].中国安全科学学报,2003,13(6):25-28. ZHU Jianhua,CHU Jiacheng.Calculation of characteristic parameters of pool fire and assessment of its thermal radiation hazard[J].China Safety Science Journal,2003,13(6):25-28.
[18]YAO Y,LI Y Z,INGASON H,et al.Numerical study on overall smoke control using naturally ventilated shafts during fires in a road tunnel [J].International Journal of Thermal Sciences,2019,140:491-504.

相似文献/References:

备注/Memo

备注/Memo:
收稿日期: 2022-03-13
* 基金项目: 应急管理部消防救援局重点攻关项目(2020XFZD18);科技部国家重点研发计划项目(2021YFC3001704)
作者简介: 何坤,博士,主要研究方向为压缩空气泡沫灭火特性、隧道火灾防控。