|本期目录/Table of Contents|

[1]解志龙.CFAST在大空间火灾模拟中的应用研究[J].中国安全生产科学技术,2012,8(4):69.
 XIE Zhi long.Application of CFAST in fire simulation of large scale buildings[J].JOURNAL OF SAFETY SCIENCE AND TECHNOLOGY,2012,8(4):69.
点击复制

CFAST在大空间火灾模拟中的应用研究
分享到:

《中国安全生产科学技术》[ISSN:1673-193X/CN:11-5335/TB]

卷:
8
期数:
2012年4期
页码:
69
栏目:
学术论著
出版日期:
2012-04-30

文章信息/Info

Title:
Application of CFAST in fire simulation of large scale buildings
作者:
解志龙
(陕西消防总队榆林市消防支队, 榆林 719000)
Author(s):
XIE Zhilong
(Yulin fire detachment of Shaanxi, Yulin 719000, China)
关键词:
CFAST大空间多区域方法区域模拟火灾
Keywords:
CFAST large scale building cellzone method zone model simulation fire
分类号:
X932
DOI:
-
文献标志码:
A
摘要:
为了实现区域模拟软件CFAST在大空间火灾模拟中的应用,深入研究多区域模拟的模拟效果,引入了均匀划分和局部加密的两种多区域模拟方法。采用与实验研究相结合的方法,与测量结果对比,发现采用均匀区域划分方法时,在满足CFAST允许的区域总数要求和每个区域符合CFAST推荐的区域尺寸比例的条件下,采用的区域越多,模拟结果越精确;同时,采用在火源附近区域分布密集的局部加密划分方法,模拟效果优于均匀划分方法,烟气层最高温度相对实验测量结果的误差仅为43%,更接近实际。
Abstract:
In order to realize the application of CFAST in fire simulation of large scale buildings, the cellzone method was taken to analyze the simulation performance. Two kinds of cellzone method were discussed, which were a large scale building being divided into spaces in uniform form and the way of partial improvement of spaces density. Experiment was done in a real large scale building. The research was combined with theoretical analysis, and the measured data was compared with the simulation result. It was found that the number of the zones adopted was in proportion to the accuracy of simulation result on conditions that the size of each cellzone was recommended in CFAST and the total number was less than 30, which was the maximum of the zones allowed in CFAST. At the same time, another conclusion was also derived that the way of partial improvement of spaces density around the fire was superior to the division in uniform form through the comparison of smoke temperature and the phenomenon. The relative error between the smoke temperature simulated in the former way and the experimental result was 43%, which indicated the former way approaches to the reality a lot and it was appropriate to simulate the fire of large scale building.

参考文献/References:

-

相似文献/References:

[1]刘博,王春雨,耿伟超,等.大空间设置上、下悬窗自然排烟效果对比研究*[J].中国安全生产科学技术,2022,18(1):87.[doi:10.11731/j.issn.1673-193x.2022.01.014]
 LIU Bo,WANG Chunyu,GENG Weichao,et al.Comparative analysis on natural smoke exhaust effect of top and bottom hung windows in large space[J].JOURNAL OF SAFETY SCIENCE AND TECHNOLOGY,2022,18(4):87.[doi:10.11731/j.issn.1673-193x.2022.01.014]

备注/Memo

备注/Memo:
-
更新日期/Last Update: 2012-05-07