|本期目录/Table of Contents|

[1]陈长坤,徐童,高飞,等.狭长空间内220 kV大截面电缆火灾燃烧特点及烟气控制实验研究*[J].中国安全生产科学技术,2023,19(5):157-163.[doi:10.11731/j.issn.1673-193x.2023.05.022]
 CHEN Changkun,XU Tong,GAO Fei,et al.Experimental study on combustion characteristics and smoke control of 220 kV cable with large cross-section in long and narrow space[J].JOURNAL OF SAFETY SCIENCE AND TECHNOLOGY,2023,19(5):157-163.[doi:10.11731/j.issn.1673-193x.2023.05.022]
点击复制

狭长空间内220 kV大截面电缆火灾燃烧特点及烟气控制实验研究*
分享到:

《中国安全生产科学技术》[ISSN:1673-193X/CN:11-5335/TB]

卷:
19
期数:
2023年5期
页码:
157-163
栏目:
职业安全卫生管理与技术
出版日期:
2023-05-31

文章信息/Info

Title:
Experimental study on combustion characteristics and smoke control of 220 kV cable with large cross-section in long and narrow space
文章编号:
1673-193X(2023)-05-0157-07
作者:
陈长坤徐童高飞左博元仪涛杜武豪
(1.中南大学 防灾科学与安全技术研究所,湖南 长沙 410075;
2.国网江苏省电力有限公司南京供电分公司,江苏 南京 210000;
3.中国能源建设集团江苏省电力设计院有限公司,江苏 南京 210000)
Author(s):
CHEN Changkun XU Tong GAO Fei ZUO Boyuan YI Tao DU Wuhao
(1.Institute of Disaster Prevention Science and Safety Technology,Central South University,Changsha Hunan 410075,China;
2.Nanjing Power Supply Company of State Grid Jiangsu Electric Power Co.,Ltd.,Nanjing Jiangsu 210000,China;
3.China Energy Const
关键词:
狭长空间220 kV大截面电缆火灾蔓延速度烟气控制
Keywords:
long and narrow space 220 kV cable with large cross-section flame spread rate smoke control
分类号:
X934
DOI:
10.11731/j.issn.1673-193x.2023.05.022
文献标志码:
A
摘要:
为避免或减小狭长空间内高压电缆发生火灾的可能性,建立实验模型,研究狭长空间内220 kV大截面电缆燃烧行为及火蔓延规律,分析电缆火灾下狭长空间顶棚温度分布特征,结合电缆燃烧过程,设置5种不同排烟风速,探究排烟风速对其排烟效率的影响。研究结果表明:大截面电缆阻燃外护套受火后会形成高温熔融物,滴落在底板上的高温熔融物燃烧形成的火焰不断撞击电缆底部,在电缆底部形成的拓展火焰持续加热,引燃电缆外护套的未燃段,进而导致电缆外护套底部火焰在热对流和辐射的作用下稳定蔓延;狭长空间顶棚温度峰值及熔滴火焰前锋位置随着电缆阻燃外护套的持续燃烧不断推移;大截面电缆火焰蔓延速度呈现先增大、后稳定、再减小趋势;电缆燃烧过程中会产生大量有毒烟气,采用侧向排烟模式能够有效降低狭长空间内烟气浓度。研究结果可为狭长空间内敷设电缆的消防排烟设计提供参考。
Abstract:
To avoid or reduce the possibility of fire on high-voltage cables in long and narrow spaces,an experimental model was built to study the combustion behavior and fire spread law of 220 kV cables with large cross-section in long and narrow space,and the temperature distribution characteristics beneath the ceiling of long and narrow space were analyzed.Combining the cable combustion process,five smoke exhaust velocities were set to study the influence of smoke exhaust velocity on the smoke exhaust efficiency.The results showed that the flame retardant outer sheath of cable with large cross-section will form high temperature melt after fire and drop on the bottom floor.The flame of high temperature melt will continuously hit the cable bottom,which will form flame expansion at the cable bottom,continue to heat and ignite the unburned section of the cable outer sheath,thus causing the lower half of the cable outer sheath to spread stably under the heat convection and radiation.After the flame retardant outer sheath of the cable burns,the peak temperature beneath the ceiling of long and narrow space and the front position of the droplet flame move with the continuous burning of the cable outer sheath.The flame spread velocity of cable with large cross-section increases first,then stabilizes,and next decreases.A large amount of toxic smoke will be produced during the cable combustion,and the lateral smoke exhaust mode can effectively reduce the smoke concentration in the narrow and long space.The results can provide reference for the fire and smoke exhaust design of cables laying in narrow and long spaces.

参考文献/References:

[1]靳忠福.高速铁路全电缆贯通线精确故障定位关键技术分析[J].铁道科学与工程学报,2021,18(3):596-604. JIN Zhongfu.Analysis of key techniques for accurate fault location of high-speed railway full cable through line [J].Journal of Railway Science and Engineering,2021,18(3):596-604.
[2]GRAYSON S J,HEES P V,GREEN A M,et al.Assessing the fire performance of electric cables (FIPEC) [J].Proceedings of Flame Retardants,2001,25(2):49-60.
[3]王蔚.聚氯乙烯电缆火灾特性及其影响因素研究[D].合肥:中国科学技术大学,2008.
[4]包光宏,冯军,唐勇.基于FIPEC试验的电缆燃烧性能研究[J].火灾科学,2011,20(3):173-178. BAO Guanghong,FENG Jun,TANG Yong.Study on fire behavior of electrical cables based on FIPEC tests [J].Fire Safety Science,2011,20(3):173-178.
[5]龚泰.渐强环形热流作用下的阻燃电缆细观膨胀与引燃机理研究[D].合肥:中国科学技术大学,2017.
[6]MEINIER R,SONNIER R,ZAVALETA P,et al.Fire behavior of halogen-free flame retardant electrical cables with the cone calorimeter[J].Journal of Hazardous Materials,2017:306-316.
[7]史聪灵,钱小东,张漪帆,等.基于火焰传播量热仪的ZR-YJLV电缆燃烧特性研究[J].中国安全生产科学技术,2020,16(S1):17-21. SHI Congling,QIAN Xiaodong,ZHANG Yifan,et al.Study on combustion characteristics of ZR-YJLV cable based on flame propagation calorimeter [J].Journal of Safety Science and Technology,2020,16(S1):17-21.
[8]LIM S J,KIM M,PARK J,et al.Flame spread over electrical wire with AC electric fields:internal circulation,fuel vapor-jet,spread rate acceleration,and molten insulator dripping[J].Combustion & Flame,2015,162(4):1167-1175.
[9]KOBAYASHI Y,HUANG X,NAKAYA S,et al.Flame spread over horizontal and vertical wires:the role of dripping and core[J].Fire Safety Journal,2017,91:112-122.
[10]ZHANG Y,ZHANG W,LI K Y,et al.Dripping behavior effects on flame propagation along electrical wires under high currents[J].Fire Safety Journal,2021,123:103368.
[11]李陈莹,陈杰,陈红,等.顶部排烟对高压电缆隧道火灾烟气运动的影响[J].消防科学与技术,2019,38(4):476-478. LI Chenying,CHEN Jie,CHEN Hong,et al.Effects of ventilation through the top vent on smoke movement in high voltage cable tunnel [J].Fire Science and Technology,2019,38(4):476-478.
[12]米红甫,刘亚玲,杨文璟,等.基于FDS的综合管廊电缆火灾烟气优化控制模式研究[J].中国安全生产科学技术,2020,16(7):100-105. MI Hongfu,LIU Yaling,YANG Wenjing,et al.Research on optimization control mode of smoke for cable fire in utility tunnel based on FDS [J].Journal of Safety Science and Technology,2020,16(7):100-105.
[13]李欣玉.综合管廊电缆舱火灾后通风系统的数值模拟与优化设计 [D].西安:西安建筑科技大学,2018.
[14]刘海静,王磊,相坤,等.综合管廊电力舱电缆燃烧温度及烟气分布试验研究[J].消防技术与产品信息,2018,31(12):5-12. LIU Haijing,WANG Lei,XIANG Kun,et al.Experimental study on cable combustion temperature and flue gas distribution in power cabin of utility tunnel [J].Fire Technique and Products Information,2018,31(12):5-12.
[15]雷鹏,陈长坤,赵冬月.纵向通风下分岔隧道火灾烟气蔓延特性及控制实验研究[J].铁道科学与工程学报,2022,19(7):2117-2124. LEI Peng,CHEN Changkun,ZHAO Dongyue.Experimental study on smoke movement characteristics and control in branched tunnel fire under longitudinal ventilation [J].Journal of Railway Science and Engineering,2022,19(7):2117-2124.
[16]严恩泽,雷蕾.L 型电缆廊道火灾温度场及烟气蔓延模拟[J].消防科学与技术,2018,37(1):37-41. YAN Enze,LEI Lei.Temperature field and smoke flow of fire in L-type cable tunnel [J].Fire Science and Technology,2018,37(1):37-41.
[17]赵永昌,朱国庆,高云骥.城市地下综合管廊火灾烟气温度场研究[J].消防科学与技术,2017,36(1):37-40. ZHAO Yongchang,ZHU Guoqing,GAO Yunji.Research on temperature field of fire smoke in urban underground utility tunnel[J].Fire Science and Technology,2017,36(1):37-40.
[18]陈长坤,徐童,陈杰,等.不同布置形式下的桥架电缆燃烧特性[J].中南大学学报(自然科学版),2022,53(11):4326-4334. CHEN Changkun,XU Tong,CHEN Jie,et al.Combustion characteristics of trays cable in different layouts[J].Journal of Central South University (Science and Technology),2022,53(11):4326-4334.
[19]YI L,WEI R,PENG J Z,et al.Experimental study on heat exhaust coefficient of transversal smoke extraction system in tunnel under fire [J].Procedia Engineering,2013,52:268-278.

相似文献/References:

备注/Memo

备注/Memo:
收稿日期: 2022-11-06
* 基金项目: 国家自然科学基金项目(72091512);国网江苏省电力有限公司科技项目(J2021105);中南大学研究生自主探索创新项目(2021zzts0234)
作者简介: 陈长坤,博士,教授,主要研究方向为火灾科学与消防工程。
更新日期/Last Update: 2023-06-12