|本期目录/Table of Contents|

[1]李军正,郑金达,魏雪,等.通信铁塔影响建筑物防雷安全计算公式之合理性探讨[J].中国安全生产科学技术,2013,9(11):162-166.[doi:10.11731/j.issn.1673-193x.2013.11.028]
 LI Jun zheng,ZHENG Jin da,WEI Xue,et al.Exploration to the rationality of computational formulae for impacting of communication towers on building lightningprotection safety[J].JOURNAL OF SAFETY SCIENCE AND TECHNOLOGY,2013,9(11):162-166.[doi:10.11731/j.issn.1673-193x.2013.11.028]
点击复制

通信铁塔影响建筑物防雷安全计算公式之合理性探讨
分享到:

《中国安全生产科学技术》[ISSN:1673-193X/CN:11-5335/TB]

卷:
9
期数:
2013年11期
页码:
162-166
栏目:
职业安全卫生管理与技术
出版日期:
2013-11-30

文章信息/Info

Title:
Exploration to the rationality of computational formulae for impacting of communication towers on building lightningprotection safety
作者:
李军正1郑金达1魏雪1周雪君1李利剑2
(1 台州市气象局,浙江台州318000;2 中国移动黄岩分公司,浙江台州318020)
Author(s):
LI Junzheng 1ZHENG Jinda 1WEI Xue 1ZHOU Xuejun 1LI Lijian 2
(1 Taizhou Meteorological Bureau,Taizhou Zhejiang 318000,China;  2 China Mobile Communications Corporation Huangyan Branch,Taizhou Zhejiang 318020,China)
关键词:
通信铁塔防雷安全年预计雷击次数计算公式合理性
Keywords:
communication tower lightningprotection safety expected annual number of lightning calculating formula rationality
分类号:
X924.4
DOI:
10.11731/j.issn.1673-193x.2013.11.028
文献标志码:
A
摘要:
以一个发生过严重雷灾事故的屋顶通信铁塔为例,分别利用国际电信联盟ITU-K56《无线通讯基站的雷电防护》和国际电报电话咨询委员会CCITT《防雷手册》中的公式计算出建筑物安装了通信铁塔后的年预计雷击次数,并将之与未安装通信铁塔时的年预计雷击次数进行对比,两者的计算结果存在显著差异。基于雷击条件相似原则,参照移动公司通信铁塔每年遭受雷击次数的实际统计数据,对这两个计算公式的合理性问题进行了探讨。研究结果表明,CCITT《防雷手册》中的计算公式更具合理性,计算结果更加接近实际值,计算方法更能准确地评估铁塔对所在区域的建筑物及电子电气设备的防雷安全所造成的影响。
Abstract:
Based on the case study of a roof communication tower which once had a serious lightningstroke accident, firstly the expected annual numbers of lightning of the building with a communication tower were calculated using two formulas: one is the ITUK56 《Protection of Radio Base Stations against Lightning Discharges》 compiled by the International Telecommunication Union; the other is the CCITT《Lightning Protection Guide》 compiled by the International Telegraph and Telephone Consultative Committee. Compared with the numbers of the building without a tower installed, the results of the two methods were significantly different. According to the similarity rule of lightningstroke conditions and the practical annual numbers of lightning of communication towers in Chinese Mobile Corporations, the rationality of the above two methodologies was discussed. It showed that CCITT《Lightning Protection Guide》 is a more reasonable and practical way to calculate the numbers of lightning and is a more accurate guidance for estimating the impacts of lightning protection for the buildings, electronic and electrical equipments nearby.

参考文献/References:

[1]张朝辉. 谈通讯铁塔可能增加雷击事故的原因[J]. 科技与生活,2011,(13):178179 ZHANG Chaohui.Analysis on reasons for the possible increase of lightningstroke accident. Technology and Life,2011,(13):178179 
[2]浙江移动通信基站防雷与接地系统工程施工验收规范[S],2003
[3]聂剑红.安全监控系统的防雷技术研究[J].中国安全生产科学技术,2009,5(6):9599  NIE Jianhong. Study on lightningprotection technology of security surveillance and control system [J].Journal of Safety Science and Technology,2009,5(6):9599
[4]郭金玉,张忠彬,孙庆云.层次分析法在安全科学研究中的应用[J].中国安全生产科学技术,2008,4(2):6973 GUO Jinyu,ZHANG Zhongbin,SUN Qingyun. Applications of AHP method in safety science[J]. Journal of Safety Science and Technology,2008,4(2):6973
[5]GB500572010 建筑物防雷设计规范[S]
[6]GB503432012 建筑物电子信息系统防雷技术规范[S]
[7]ITUK56 无线通讯基站的雷电防护[S]
[8]CCITT. 防雷手册
[9]SDJ779,电力设备过电压保护技术规程
[10]尹晓霞,邵明伟. 浅谈基站的防雷整改措施[J]. 光纤与电缆及其应用技术,2011,(3):3943 YIN Xiaoxia,SHAO Mingwei. The rectification measures for mobile basestation lightning protection[J]. Optical Fiber & Electric Cable and Their Applications,2011,(3):3943
[11]聂剑红.油田集输站安全监控系统防雷分析与设计[J].中国安全生产科学技术,2008,4(3):3437 NIE Jianhong. Study on lightningprotection technology of oil field security surveillance and control system [J].Journal of Safety Science and Technology,2008, 4(3):3437〖FL)〖HJ〖HT〖ST〖WT

相似文献/References:

备注/Memo

备注/Memo:
-
更新日期/Last Update: 2013-11-30